Model | OLS6000E |
Capacity (VA/W) | 6000VA / 5400W |
Typology | Online (Double Conversion) |
Energy-Saving Technology | Yes, ECO Mode Efficiency > 96% |
Input | |
Input Type | Terminal Block |
Frequency Range | 45 ~ 65Hz |
Output | |
UPS Outlets (Numbers) | Terminal Block |
On Battery Output Voltage | Pure Sine Wave at 208, 220, 230, 240 Vac (Configurable) |
On Battery Output Voltage Distortion (@Nominal Battery Voltage) | < 2%(Linear Load), <5%(Non-Linear Load) |
On Battery Output Frequency | 50 Hz / 60 Hz (Auto-Sensing or Configurable) ± 0.5% |
Transfer Time (Typical) | 0 ms |
Overload Protection | Line Mode: 10 minutes minimum,then transfer to bypass @105%<Load≤125%; 1 minute minimum,then transfer to bypass @125<Load≤150% ; 10 second minimum then transfer to bypass @Load>150%; 1 second minimum then transfer to bypass@Load>170% Battery Mode: 2 minutes minimum,then shutdown @105%150% |
Short Circuit Protection | UPS Output Cut off Immediately or Circuit Breaker Protection |
Surge Protection and Filtering | |
Surge Protection | Yes |
DSL/ Phone/ Fax/ Modem protection | No |
Battery | |
Sealed Maintenance Free Lead Acid Battery | (20) 12V / 7AH |
Typical Recharge Time | 7 Hours |
Runtimes | |
Half load-Full load (mins) | 15/5 |
Status Indication | |
Indicators | Power On, Line Mode, Battery Mode, Bypass Mode, ECO Mode,C/F Mode, Fault, Replace Battery |
Audible Alarms | Battery Mode, Battery Low, Overload, UPS Fault, Replace Battery |
Communication | |
Power Management Software | PowerPanel® Business Edition |
Management | |
Self-Test | Yes |
Auto-Charge/ Auto-Restart | Yes |
Auto-Overload Recovery | Yes |
Cold Start (DC Start) | Yes |
Connectivity Ports | (1) Serial Port (RS232), (1) USB Port, (1) EPO/ROO |
SNMP/ HTTP Capable | Optional |
Dimensions | 708 x 260 x 550 mm |
Weight | 70 kg |
Đánh giá